    Tests on XLPE-insulated cable arcing faults and arc-proofing

  • Author

    Koch, Bohdan

  • Author_Institution
    IREQ, Varennes, Que., Canada
  • Volume
    3
  • Issue
    4
  • fYear
    1988
  • fDate
    10/1/1988 12:00:00 AM
  • Firstpage
    1289
  • Lastpage
    1295
  • Abstract
    Questions about the adequacy of arc-proofing have arisen in connection with underground systems using XLPE-insulated cables, because of an increasing number of arc faults. Extensive testing at available short-circuit-current levels of 8 kA is described. The results indicate that a minimum safe distance of 50 cm should be maintained for nonarc-proofed equipment. For equipment protected with arc-resistant tape, this distance can be substantially reduced. Standard tests based on the use of faulted XLPE cable ends are proposed to verify arc-proofing effectiveness and the arc-resistance of materials
  • Keywords
    arcs (electric); cable insulation; cable testing; organic insulating materials; polymers; short-circuit currents; underground cables; 8 kA; arc faults; arc-proofing; arc-resistant tape; short-circuit-current levels; underground XLPE-insulated cables; Building materials; Circuit faults; Circuit testing; Concrete; Hazardous materials; Materials testing; Power cable insulation; Power cables; Protection; Trees - insulation;