DocumentCode :
853584
Title :
Effect of transmission line loading on the performance characteristics of polyphase distance relay elements
Author :
Marttila, R.J.
Author_Institution :
Ontario Hydro Res., Toronto, Ont., Canada
Volume :
3
Issue :
4
fYear :
1988
fDate :
10/1/1988 12:00:00 AM
Firstpage :
1466
Lastpage :
1474
Abstract :
The performance characteristics of a polyphase element for the detection of phase faults is examined. The results show the effect of transmission line loading and reach setting on the detection characteristics of forward faults. The polyphase element exhibits tendencies to under-reach for far-end as well as close-in faults with zero fault resistance, under some conditions. The results are presented in a manner that facilitates ready assessment of the expected performance of a polyphase element in a particular application
Keywords :
fault location; power transmission lines; relay protection; phase fault detection; polyphase distance relay elements; transmission line loading; Fault detection; Impedance; Phase detection; Power system modeling; Power system relaying; Protection; Protective relaying; Transmission line measurements; Transmission lines; Voltage;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/61.193945
Filename :
193945
Link To Document :
بازگشت