Abstract :
Several low frequencies of the current waveform in distribution feeders exhibit modified behavior under fault conditions. Two frequencies, 180 Hz and 210 Hz, were selected for study owing to the strong magnitude variations associated with arcing faults at these frequencies. A hierarchical algorithm with adaptive characteristics is presented along with the performance results for its application at these low frequencies. The various parameters that affect the sensitivity of the algorithm are discussed. The results of tests using recorded field data are given, and the effects of using a digital filter front end for the algorithm are also discussed
Keywords :
arcs (electric); distribution networks; fault location; 180 Hz; 210 Hz; arcing fault detection; digital filter; distribution feeders; distribution networks; fault location; hierarchical algorithm; low frequency current; performance; tests; Detectors; Digital relays; Electrical fault detection; Fault detection; Frequency; Impedance; Monitoring; Protection; Protective relaying; Student members;