DocumentCode :
853663
Title :
`Decoupled method´ for studying large interconnected grounding systems using microcomputers. I. Fundamentals
Author :
Sobral, S.T. ; Fleury, Vasco G P ; Villalba, J.R. ; Mukhedkar, D.
Author_Institution :
IESA-Int. de Eng. SA, Rio De Janeiro, Brazil
Volume :
3
Issue :
4
fYear :
1988
fDate :
10/1/1988 12:00:00 AM
Firstpage :
1536
Lastpage :
1544
Abstract :
When the common matrix representation of the complete ground circuit is used, the quality of the solution decreases with the size of the circuit, owing to the propagation of the relative error of each circuit element. A decoupled method is presented that comprises a set of procedures allowing the determination of an equivalent circuit generally 10-60 times smaller than the original one. The flowchart of the corresponding computer program is also presented. The reduced size of this equivalent circuit avoids the error propagation and allows even huge ground systems to be studied using microcomputers
Keywords :
earthing; microcomputer applications; power system analysis computing; power system protection; computer program; decoupled method; earthing; equivalent circuit; ground circuit; interconnected grounding systems; matrix; microcomputers; power system analysis computing; power system protection; Conductors; Distributed parameter circuits; Grounding; Integrated circuit interconnections; Microcomputers; Power system interconnection; Power transmission lines; Substations; Transmission line theory; Wires;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/61.193953
Filename :
193953
Link To Document :