Title :
Derivation of synchronous machine parameters from tests
Author :
de Mello, F.P. ; Ribeiro, J.R.
Author_Institution :
Power Technologies, Inc., Schenectady, N.Y.
fDate :
7/1/1977 12:00:00 AM
Abstract :
This paper describes a test procedure for derivation of synchronous machine parameters. The tests can be conducted with ease and without hazard on generators in utility systems. Unlike textbook methods involving short circuit and slip tests which are inconvenient and hazardous, the proposed method involves simple procedures, which can be implemented in normal operation of the machine.
Keywords :
Circuit breakers; Circuit simulation; Circuit testing; Hazards; Machine windings; Power system dynamics; Power system stability; Synchronous machines; System testing; Voltage;
Journal_Title :
Power Apparatus and Systems, IEEE Transactions on
DOI :
10.1109/T-PAS.1977.32443