DocumentCode :
853834
Title :
Power dissipation characteristics of zinc-oxide arresters for HVDC systems
Author :
Horiuchi, S. ; Ichikawa, Fusao ; Mizukoshi, A. ; Kurita, K. ; Shirakawa, S.
Author_Institution :
Tokyo Electr. Power Co. Inc., Japan
Volume :
3
Issue :
4
fYear :
1988
fDate :
10/1/1988 12:00:00 AM
Firstpage :
1666
Lastpage :
1671
Abstract :
The voltage waveforms applied to HVDC surge arresters do not have a simple sinusoidal shape, so that the leakage current contains high-frequency components. The power dissipation characteristics of a thyristor valve arrester were measured using a 1/25 prorated arrester section with a 5 kV/500 kW thyristor bridge. High-frequency power dissipation characteristics of the zinc-oxide elements were measured, and it was found that the high-frequency power dissipation of the thyristor valve arrester is larger than that of an AC system arrester. The determination of the equivalent continuous operating voltage for the performance testing of an HVDC arrester is considered
Keywords :
DC power transmission; power system protection; surge protection; testing; zinc compounds; 5 kV; 500 kW; DC power transmission; HVDC systems; ZnO; leakage current; performance testing; power dissipation; power system protection; surge arresters; thyristor bridge; thyristor valve arrester; voltage waveforms; Arresters; HVDC transmission; Leakage current; Power dissipation; Power measurement; Shape; Surges; Thyristors; Valves; Voltage;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/61.193969
Filename :
193969
Link To Document :
بازگشت