DocumentCode :
853864
Title :
Use of integral arc models in circuit breaker testing and development
Author :
Widl, W. ; Kirchesch, P. ; Egli, W.
Author_Institution :
Brown Boveri & Co. Ltd., Baden, Switzerland
Volume :
3
Issue :
4
fYear :
1988
fDate :
10/1/1988 12:00:00 AM
Firstpage :
1685
Lastpage :
1691
Abstract :
The extended Mayr equation for the electric arc was used to develop an evaluation technique for determining the relevant arc parameters separately for each single short line fault (SLF) test. Thus it is possible to calculate the results expected from these tests under changed circuit conditions. The main advantage is an increase of the information gained from the tests. Special care was taken to choose measurement and calculation methods that are sufficiently robust for application in power tests. Only the arc voltage before current zero, the applied inherent dI/dt, and the circuit elements are needed as input data. The validity of the technique was tested by a sensitivity analysis and several comparisons between calculated and measured results. The method is already being routinely applied for full-scale SF6 breaker testing and development
Keywords :
arcs (electric); circuit breakers; fault currents; testing; SF6 circuit break; SLF test; arc voltage; circuit breaker testing; current zero; extended Mayr equation; integral arc models; single short line fault; Circuit breakers; Circuit faults; Circuit testing; Mathematical model; Power measurement; Robustness; Scattering parameters; Sensitivity analysis; Sulfur hexafluoride; Voltage;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/61.193972
Filename :
193972
Link To Document :
بازگشت