Voltage escalation in vacuum switching operations
Author :
Greenwood, Allan ; Glinkowsk, Mietek
Author_Institution :
Dept. of Electr. Power Eng., Rensselaer Polytech., Troy, NY, USA
Volume :
3
Issue :
4
fYear :
1988
fDate :
10/1/1988 12:00:00 AM
Firstpage :
1698
Lastpage :
1706
Abstract :
The ability of vacuum switching devices to interrupt high-frequency currents can lead to repeated prestrikes and clearings when such switches are being closed and repeated reignitions and clearings when the switches are opening. Attention is focused on the interruption of a motor inrush current (aborted starts), where the successive trapping of magnetic stored energy in the motor winding and its subsequent release to the motor and cable capacitance can result in a sequence of escalating voltage surges. Of particular concern is the sudden collapse of voltage when sequential reignitions occur and the impact of this on the interturn insulation of the motor winding. The authors report on simulated tests with circuit breakers of different manufacturers and attempt to analyze cause and effect with respect to the magnitudes of the voltages developed and the characteristics of the switch. Particular attention is given to the rate of dielectric recovery of the contact gap and the dI/dt interrupting capability of the switch
Keywords :
circuit breakers; electric motors; starting; vacuum apparatus; HF current interruption; circuit breakers; contact gap; dielectric recovery; motor inrush current; vacuum switching devices; voltage escalation; Analytical models; Capacitance; Circuit breakers; Circuit simulation; Circuit testing; Dielectrics and electrical insulation; Surges; Switches; Virtual manufacturing; Voltage;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/61.193974
Filename :
193974
Link To Document :
بازگشت