Prediction of the friction factor in laminar flow through three-phase pipe-type power transmission line
Author :
Koci, P.F. ; Glicksman, L.R. ; Rohsenow, W.M. ; Buckweitz, M.D.
Author_Institution :
Massachusetts Institute of Technology, Cambridge, Massachusetts
Volume :
96
Issue :
4
fYear :
1977
fDate :
7/1/1977 12:00:00 AM
Firstpage :
1305
Lastpage :
1310
Abstract :
The relationship between the friction factor and the Reynolds number for laminar isothermal fully developed flow through several cable configurations of a three-phase pipe-type electrical power transmission line is predicted. The predictions agree well with data taken from scaled down and full scale model tests. The RMS error is 15.4%. The friction factor varies widely among the configurations and therefore, Since the cable configuration on a real transmission system is arbitrary, the higher friction factor values found for the open triangular cable configuration should be used for design purposes.
Keywords :
Friction; Heat transfer; Heating; Hydraulic diameter; Petroleum; Power cables; Power system modeling; Power transmission lines; Predictive models; Testing;