DocumentCode :
854132
Title :
Aging effects of conductor surface conditions on DC corona characteristics
Author :
Suda, Tomotaka ; Hirayama, Yoshiyuki ; Sunaga, Yoshitaka
Author_Institution :
Central Res. Inst. of Electr. Power Ind., Tokyo, Japan
Volume :
3
Issue :
4
fYear :
1988
fDate :
10/1/1988 12:00:00 AM
Firstpage :
1903
Lastpage :
1912
Abstract :
Aging effects are investigated by means of comparing a 7 yr-old conductor of the Takeyama HVDC test line with a new one. Long-term comparative tests were carried out in monopolar and bipolar arrangements. Corona currents of the aged conductor were greater than those of the new one by 1~2 times, ~2 times and 10~30% in the +250 kV monopolar, -250 kV monopolar, and ±250 kV bipolar arrangements, respectively. These results contrast with AC corona currents that decrease due to aging. Artificial pollution experiments, based on the chemical analysis of substances on the aged conductor, reveal that both the corona currents and flow currents at ground level increase as the amount of pollution, especially carbon, increases and that the differences between the monopolar and bipolar arrangements in the comparative tests can be explained by relations between the maximum conductor surface gradient and the corona onset gradient
Keywords :
ageing; corona; overhead line conductors; 250 kV; DC corona characteristics; Takeyama HVDC test line; artificial pollution tests; bipolar arrangements; chemical analysis; conductor surface conditions; corona currents; flow currents; monopolar arrangement; Aging; Conductors; Corona; HVDC transmission; Pollution; Rough surfaces; Surface contamination; Surface discharges; Surface roughness; Testing;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/61.193999
Filename :
193999
Link To Document :
بازگشت