• DocumentCode
    854166
  • Title

    Fast generator protection against internal asymmetrical faults

  • Author

    Dash, P.K. ; Malik, O.P. ; Hope, G.S.

  • Author_Institution
    The University of Calgary, Calgary, Canada
  • Volume
    96
  • Issue
    5
  • fYear
    1977
  • Firstpage
    1498
  • Lastpage
    1506
  • Abstract
    An on-line digital computer technique for the protection of a generator against internal asymmetrical faults is described in this paper. The proposed technique relies on the detection of a second harmonic component in the field current at the onset of a fault in the armature winding. Discrimination against external faults is achieved by monitoring the direction of the negative sequence power flow at the machine terminals. Tests have been conducted on a laboratory synchronous generator for various types of internal and external faults. Results show that the total time for internal fault detection and tripping is well within half a cycle of the 60 Hz signal. A simple extension to negative sequence relaying and loss of excitation relaying is proposed.
  • Keywords
    Circuit faults; Digital relays; Electrical fault detection; Fault detection; Load flow; Protection; Protective relaying; Stators; Synchronous generators; Testing;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/T-PAS.1977.32478
  • Filename