DocumentCode :
854166
Title :
Fast generator protection against internal asymmetrical faults
Author :
Dash, P.K. ; Malik, O.P. ; Hope, G.S.
Author_Institution :
The University of Calgary, Calgary, Canada
Volume :
96
Issue :
5
fYear :
1977
Firstpage :
1498
Lastpage :
1506
Abstract :
An on-line digital computer technique for the protection of a generator against internal asymmetrical faults is described in this paper. The proposed technique relies on the detection of a second harmonic component in the field current at the onset of a fault in the armature winding. Discrimination against external faults is achieved by monitoring the direction of the negative sequence power flow at the machine terminals. Tests have been conducted on a laboratory synchronous generator for various types of internal and external faults. Results show that the total time for internal fault detection and tripping is well within half a cycle of the 60 Hz signal. A simple extension to negative sequence relaying and loss of excitation relaying is proposed.
Keywords :
Circuit faults; Digital relays; Electrical fault detection; Fault detection; Load flow; Protection; Protective relaying; Stators; Synchronous generators; Testing;
fLanguage :
English
Journal_Title :
Power Apparatus and Systems, IEEE Transactions on
Publisher :
ieee
ISSN :
0018-9510
Type :
jour
DOI :
10.1109/T-PAS.1977.32478
Filename :
1602080
Link To Document :
بازگشت