• DocumentCode
    854226
  • Title

    Contamination performance of HVDC station post insulators

  • Author

    Baker, A.C. ; Zaffanella, L.E. ; Anzivino, L.D. ; Schneider, H.M. ; Moran, J.H.

  • Author_Institution
    Laap Insulator, Leroy, NY, USA
  • Volume
    3
  • Issue
    4
  • fYear
    1988
  • fDate
    10/1/1988 12:00:00 AM
  • Firstpage
    1968
  • Lastpage
    1975
  • Abstract
    The effect of shed configuration on the contamination performance of post insulators for HVDC converter stations is reported. Field measurements of contamination severity are used to define the contaminant levels utilized in artificial contamination tests made with the clean fog method. Test results for naturally contaminated post insulators are also presented. The influence of shape parameters on the accumulation of contaminant is also investigated by means of a dust deposit chamber. Improvements in withstand capability of post insulators with special treatments are described
  • Keywords
    insulation testing; insulators; HVDC converter stations; HVDC station post insulators; artificial contamination tests; clean fog method; contamination performance; shape parameters; shed configuration; withstand capability; Circuit testing; Costs; Dielectrics and electrical insulation; Flashover; HVDC transmission; Insulator testing; Pollution measurement; Shape measurement; Surface contamination; Voltage;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.194007
  • Filename