DocumentCode
854247
Title
A comparative program on HVDC contamination tests
Author
Hasegawa, Y. ; Naito, E. ; Arakawa, K. ; Schneider, H.M. ; Zaffanella, L.E.
Author_Institution
NGK Insulators Ltd., Nagoya, Japan
Volume
3
Issue
4
fYear
1988
fDate
10/1/1988 12:00:00 AM
Firstpage
1986
Lastpage
1995
Abstract
The reproducibility of artificial contamination tests for insulators energized with HVDC is investigated in a series of comparative tests performed at two different laboratories using clean fog and predeposited contaminants. The effects of fog generation, type of inert material, single vs. multiple string test configurations, and characteristics of the power supply are reported. The controls required to achieve reproducible results are defined for tests on ceramic insulators, and the limitations in applying these controls to tests on nonceramic insulators are described
Keywords
insulation testing; insulators; HVDC contamination tests; artificial contamination tests; ceramic insulators; clean fog; insulators; nonceramic insulators; power supply characteristics; predeposited contaminants; Contamination; Electrostatics; Flashover; HVDC transmission; Insulation testing; Insulator testing; Laboratories; Performance evaluation; Reproducibility of results; Voltage;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/61.194009
Filename
194009