DocumentCode
854383
Title
Dynamic performance of an HVDC quasi 24-pulse series tapping station
Author
Arabi, S. ; Tarnawecky, M.Z. ; Iravani, M.R.
Author_Institution
Dept. of Electr. & Comput. Eng., Concordia Univ., Montreal, Que., Canada
Volume
3
Issue
4
fYear
1988
fDate
10/1/1988 12:00:00 AM
Firstpage
2112
Lastpage
2118
Abstract
The dynamic performance of quasi-24-pulse series tapping with a weak AC system is investigated. A small-signal analysis of the scheme is presented and the controls are optimized. Other applications as well as the effect of the location of the tap on the DC harmonics entering the DC line sections are discussed. Digital simulation studies are performed on a 10% tap assumed in the Bipole II of the Nelson River HVDC system. The simulation results support the theoretical results and indicate satisfactory performance of the scheme in response to various disturbances in the system
Keywords
DC power transmission; power convertors; Bipole II; DC harmonics; HVDC quasi 24-pulse series tapping station; Nelson River HVDC system; digital simulation; small-signal analysis; weak AC system; Bridge circuits; Differential equations; HVDC transmission; Power generation economics; Power harmonic filters; Power system dynamics; Power system harmonics; Reactive power; Signal analysis; Voltage;