DocumentCode :
854533
Title :
A feasibility study and experiments on a cryoresistive transformer cooled at -150 degree c with fluorocarbon
Author :
Inui, Y. ; Tsutsumi, Y. ; Miyashita, T. ; Masuda, S. ; Sakamoto, T. ; Kako, Y. ; Okuyama, K.
Author_Institution :
Hitachi Ltd., Hitachi, Ibaraki, Japan
Volume :
96
Issue :
6
fYear :
1977
Firstpage :
1831
Lastpage :
1839
Abstract :
The feasibility of a new type cryoresistive transformer, which is operated at -150°C and has a higher efficiency and some weight and size merits compared to the conventional oil cooled transformer, is examined. This transformer has a new cooling system in which the latent heat of evaporation of L.N.G. is used instead of a refrigerator. In addition, because of the low operating temperature, some new materials which are not commonly used in oil cooled transformer, such as liquid fluorocarbon 12 and a composite paper made of a non-woven cloth and apolyethylene film, are adopted. A 1200 KVA experimental transformer wsa built and from the experimental results, it may be concluded that this new type cryoresistive transformer can be used as a power transformer.
Keywords :
Aluminum; Conductors; Coolants; Cooling; Copper; Ocean temperature; Oil insulation; Petroleum; Power generation; Power transformer insulation;
fLanguage :
English
Journal_Title :
Power Apparatus and Systems, IEEE Transactions on
Publisher :
ieee
ISSN :
0018-9510
Type :
jour
DOI :
10.1109/T-PAS.1977.32516
Filename :
1602118
Link To Document :
بازگشت