DocumentCode :
856802
Title :
Air quality control in control rooms [of paper mills]
Author :
Osborne, Michael W.
Author_Institution :
Purafil Inc., Doraville, GA, USA
Volume :
32
Issue :
2
fYear :
1996
Firstpage :
443
Lastpage :
448
Abstract :
Current paper mill-wide preventive maintenance programs may be lacking a critical, cost and labor-cutting component: the use of “environmental control” to prevent corrosion of electronic and electrical equipment. Field results indicate that from 30 to 40 percent of computer board failures are directly due to corrosion. This corrosion can be prevented by controlling the quality of the air in rooms where electronics are located. In this paper, environmental specifications are discussed by which the environmental conditions within the electronics rooms can be measured and compared to established ISA standards. Case studies have shown that controlling environmental conditions can substantially reduce unnecessary repair and maintenance costs associated with electronic´s failure-and thus should be aggressively incorporated into every mill´s preventive maintenance program
Keywords :
air conditioning; cooling; environmental engineering; industrial control; maintenance engineering; paper industry; ISA standards; air quality control; control rooms; corrosion prevention; electronics failure; electronics rooms; environmental control; environmental specifications; paper mills; preventive maintenance; repair; Control systems; Corrosion; Costs; Distributed control; Gases; Instruction sets; Measurement standards; Preventive maintenance; Process control; Quality control;
fLanguage :
English
Journal_Title :
Industry Applications, IEEE Transactions on
Publisher :
ieee
ISSN :
0093-9994
Type :
jour
DOI :
10.1109/28.491495
Filename :
491495
Link To Document :
بازگشت