Title :
Transient response of a static VAr shunt compensator
Author :
Best, Robert Andrew ; Parra, Hector Zelaya-De La
Author_Institution :
Sch. of Electron. & Electr. Eng., Birmingham Univ., UK
fDate :
5/1/1996 12:00:00 AM
Abstract :
A typical static VAr shunt compensator has been analyzed so that the step response and steady-state errors can be identified. The results show that the steady-state error is dependent upon the error in the measurement of the currents´ phase alone. They also show that an unstable condition can occur, though it should rarely arise in practice. All the theory was verified on a low power (240 V, 3 A) system
Keywords :
control system analysis; power system control; power system stability; power system transients; reactive power control; static VAr compensators; step response; transient response; 240 V; 3 A; current phase measurement error; power systems; stability; static VAr shunt compensator; steady-state error; step response; transient response; Feedback; Load management; Phase measurement; Power factor correction; Reactive power; Shunt (electrical); Static VAr compensators; Steady-state; Transient response; Voltage;
Journal_Title :
Power Electronics, IEEE Transactions on