DocumentCode :
86005
Title :
Evaluation of Differential Pressure Setpoint of Chilled Water Pumps in Clean Room HVAC Systems for Energy Savings in High-Tech Industries
Author :
Chun-Lien Su ; Kuen-Tyng Yu
Author_Institution :
Dept. of Marine Eng., Nat. Kaohsiung Marine Univ., Kaohsiung, Taiwan
Volume :
49
Issue :
3
fYear :
2013
fDate :
May-June 2013
Firstpage :
1015
Lastpage :
1022
Abstract :
Variable-frequency speed control technologies are widely used in chilled water pumps in clean room heating, ventilation, and air-conditioning (HVAC) systems in high-tech industries to reduce energy consumption. Pumps with variable frequency drivers work based on the reading from the differential pressure sensor placed between the chilled water supply and return lines before the secondary and tertiary pumps. The determination of the differential pressure setpoint must take pipeline topology and material, chilled water flow demand, heat loading, and system equipment aging into account so as to provide operating flexibility for energy conservation while ensuring the secure operation of the clean room. To enhance clean room energy efficiency, a new methodology is proposed in this paper for determining the proper chilled piping pressure setpoint for the pumps. The mathematic model of head loss required for generic secondary and tertiary chilled networks widely used in clean rooms is derived using the Hazen-Williams formula principle. The field testing results confirm the validity of the proposed approach through a practical clean room HVAC system for electronic semiconductor manufacturing, and the energy savings and investment benefits due to the use of the proper differential pressure setpoint are determined.
Keywords :
HVAC; clean rooms; energy conservation; energy consumption; pipelines; pressure sensors; pumps; variable speed drives; water supply; Hazen-Williams formula principle; chilled piping pressure setpoint; chilled water flow demand; chilled water pumps; chilled water supply; clean room HVAC system; clean room heating ventilation and air-conditioning system; differential pressure sensor; differential pressure setpoint; electronic semiconductor manufac- turing; energy consumption reduction; energy saving; field testing; heat loading; high-tech industries; mathematic model; pipeline topology; system equipment aging; variable frequency drivers; variable-frequency speed control technology; Fitting; Industries; Pipelines; Temperature measurement; Valves; Water heating; Chilled water pumps; clean room; differential pressure; energy savings; field testing; high-tech industries;
fLanguage :
English
Journal_Title :
Industry Applications, IEEE Transactions on
Publisher :
ieee
ISSN :
0093-9994
Type :
jour
DOI :
10.1109/TIA.2013.2251992
Filename :
6476673
Link To Document :
بازگشت