• DocumentCode
    865820
  • Title

    A New Strategy for Determining Fault Zones in Distance Relays

  • Author

    Gilany, Mahmoud ; Al-Kandari, Ahmed M. ; Madouh, Jamal Y.

  • Author_Institution
    Dept. of Electr. Eng., Coll. of Technol. Studies, Shuwaikh
  • Volume
    23
  • Issue
    4
  • fYear
    2008
  • Firstpage
    1857
  • Lastpage
    1863
  • Abstract
    A new strategy (denoted P-SS) for estimating the correct fault zone in distance relays is introduced. The main difference between the P-SS and conventional setting strategies is that the P-SS does not depend on fixed boundaries for backup zones. It depends on exchanging information between local relays in the same station in addition to a command from the remote end relay. With the proposed strategy, zone-1 covers the entire length of the protected line, zone-2 covers the entire length of any next line irrespective of its length, and zone-3 covers the entire length of any line next to zone-2. The governing rules for the proposed strategy are presented. The strategy is examined against a wide range of setting problems of a real part of a high-voltage network with real relay settings. The results confirm that the P-SS achieves the required accurate, sensitive, and selective relay operation.
  • Keywords
    fault diagnosis; power system protection; relay protection; P-SS; backup zones; distance relays; fault zones; high-voltage network; power system protection; real relay settings; Availability; Circuit faults; Impedance; Integrated circuit interconnections; Power system faults; Power system protection; Power system relaying; Protective relaying; Relays; Substation protection; Distance relays; fault zones; pilot schemes; setting problems;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/TPWRD.2008.2002871
  • Filename
    4626360