• DocumentCode
    875131
  • Title

    Design of novel structure current transformer with shielding coils for overcoming the saturation of core

  • Author

    Yu, Haiyu ; Yuan, Jiansheng ; Zou, Jun

  • Author_Institution
    Dept. of Electr. Eng., Tsinghua Univ., Beijing
  • Volume
    42
  • Issue
    4
  • fYear
    2006
  • fDate
    4/1/2006 12:00:00 AM
  • Firstpage
    1431
  • Lastpage
    1434
  • Abstract
    The core saturation of current transformers is one of the key obstructions in the development of highly reliable protective approaches and devices of power systems. A novel structure current transformer with shielding coils is introduced and analyzed in this paper. The coils are enwound outside the measurement winding of the current transformer, and each couple of coils are located at the opposite position relative to the diameter of the core, and connected in opposed-polarity. With the opposed-polarity connecting coils the magnetic field in the core produced by its adjacent phase current in a three-phase system can be shielded, so that the core saturation can be avoided. However, the coils do not influence the main magnetic flux that is caused only by the same phase current
  • Keywords
    coils; current transformers; magnetic flux; magnetic shielding; transformer cores; core saturation; current transformer; electromagnetic shielding; opposed-polarity connecting coils; power systems protection device; shielding coils; three-phase system; Coils; Current transformers; Magnetic analysis; Magnetic cores; Magnetic field measurement; Power system analysis computing; Power system measurements; Power system protection; Power system reliability; Transformer cores; Current transformer; electromagnetic shielding; nonlinear; saturation;
  • fLanguage
    English
  • Journal_Title
    Magnetics, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9464
  • Type

    jour

  • DOI
    10.1109/TMAG.2006.872478
  • Filename
    1608485