    Transmission voltage recovery delayed by stalled air conditioner compressors

  • Author

    Williams, Bradley R. ; Schmus, Wayne R. ; Dawson, Douglas C.

  • Author_Institution
    Southern California Edison Co., Rosemead, CA, USA
  • Volume
    7
  • Issue
    3
  • fYear
    1992
  • fDate
    8/1/1992 12:00:00 AM
  • Firstpage
    1173
  • Lastpage
    1181
  • Abstract
    Southern California Edison Company (SCE) has experienced delayed voltage recovery following fault clearing on the transmission system. The authors describe these occurrences and document the studies which successfully modeled the voltage recovery process. The studies showed how the stalling of single-phase air conditioner compressors following a power system fault was the root cause of delayed voltage recovery. Tests of air conditioner response to voltage dips are documented. The results of these tests are used to derive the mathematical load models used in voltage recovery studies
  • Keywords
    air conditioning; compressors; electrical faults; power systems; transmission networks; Southern California Edison Company; delayed voltage recovery; fault clearing; mathematical load models; power system fault; stalled air conditioner compressors; transmission system; Air conditioning; Compressors; Delay; Impedance; Induction motors; Load modeling; Low voltage; Power system faults; Synchronous motors; Testing;