Abstract :
Air-magnetic circuit breakers are widely used for short-circuit protection in dc electric railways or industrial plants. The well-known drawbacks of these breakers are mainly a slow breaking action, a short lifetime, and high maintenance costs due to the destructive effects of the arc. The use of power semiconductors in a full-static circuit breaker configuration allows the elimination of these disadvantages but is limited by excessive conduction losses. The paper will present the study of a so-called hybrid breaker, drawing its name from the combination of a high-speed mechanical switch and a bi-directional integrated gate-controlled thyristor assembly connected in parallel. The paper also includes experimental results from a prototype real scale.
Keywords :
air blast circuit breakers; electrical contacts; power semiconductor switches; thyristors; DC hybrid circuit breaker; IGCT; air magnetic circuit breaker; arc destructive effects; dc electric railways; full-static circuit breaker; high-speed mechanical switch; industrial plants; integrated gate commutated thyristors; power semiconductors; short-circuit protection; ultrafast contact opening; Assembly; Bidirectional control; Circuit breakers; Costs; Industrial plants; Power semiconductor switches; Protection; Prototypes; Rail transportation; Thyristors; Arcless interruption; fault current limiter; hybrid high-speed circuit breaker; integrated gate-controlled thyristor (IGCT); mechanical switch; metal-oxide varistor;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/TPWRD.2006.870981
Filename :
1610674
Link To Document :
بازگشت