• DocumentCode
    880895
  • Title

    Field experiences with measurements of dielectric response in frequency domain for power transformer diagnostics

  • Author

    Blennow, Jorgen ; Ekanayake, Chandima ; Walczak, Kzysztof ; Garcia, Belen ; Gubanski, Stanislaw M.

  • Author_Institution
    Dept. of Electr. Power Eng., Chalmers Univ. of Technol., Gothenburg, Sweden
  • Volume
    21
  • Issue
    2
  • fYear
    2006
  • fDate
    4/1/2006 12:00:00 AM
  • Firstpage
    681
  • Lastpage
    688
  • Abstract
    Some new methods, based on characterization of the dielectric response of transformer insulation in time and frequency domains, have been pointed out by CIGRE as suitable to assess moisture content in pressboard and paper. Measuring devices available today on the market are quite robust in field conditions; however there is a risk that undesired internal and external factors might influence the measurements. These influences can lead to mistaken interpretation of insulation wetness. Operators should therefore be aware of the risks appearing at different measuring conditions and of the precautions that can be taken to minimize their effects. This work presents a systematic investigation on the influence of some factors on the results of dielectric response measurements in field conditions. The errors that can be committed during the measurements if certain precautions are not taken, with different equipment connected in parallel, are evaluated. The influence of rain and electromagnetic disturbances are also analyzed proposing solutions to attenuate their effects. Finally, a discussion on the influence of temperature distribution follows. The work is concentrated on frequency response measurements, although some results from the use of polarization and depolarization current technique are also discussed.
  • Keywords
    dielectric measurement; moisture; power transformer insulation; temperature distribution; CIGRE; depolarization current technique; dielectric response measurement; electromagnetic disturbance; moisture content; polarization current technique; power transformer diagnostics; temperature distribution; transformer insulation; Dielectric measurements; Dielectrics and electrical insulation; Electromagnetic measurements; Frequency domain analysis; Frequency measurement; Moisture; Power measurement; Power transformer insulation; Power transformers; Robustness; Field measurements; frequency domain spectroscopy; oil-paper insulation; transformer diagnostics; water content;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/TPWRD.2005.861231
  • Filename
    1610679