    System impacts evaluation of a single-phase traction load on a 115-kV transmission system

  • Author

    Sutherland, Peter E. ; Waclawiak, Marek ; McGranaghan, Mark F.

  • Author_Institution
    GE Energy Services, Schenectady, NY, USA
  • Volume
    21
  • Issue
    2
  • fYear
    2006
  • fDate
    4/1/2006 12:00:00 AM
  • Firstpage
    837
  • Lastpage
    844
  • Abstract
    The system impact of a new transit substation may include harmonic distortion, voltage unbalance, and flicker. Measurements were taken at a similar substation, and system simulations were performed for the planned substation. It was found that the Metro North train load produced significant levels of third harmonic current. Resonances in the 115-kV system were simulated and found to be at frequencies which are not critical. A third harmonic filter is needed in order to meet IEEE 519 requirements. Unbalance and flicker were found to be negligible.
  • Keywords
    harmonic distortion; rapid transit systems; substations; traction power supplies; transmission networks; 115 kV; IEEE 519 requirements; Metro North train load; flicker; harmonic current; harmonic distortion; harmonic filter; single-phase traction load; system impacts evaluation; transit substation; transmission systems; voltage unbalance; Harmonic distortion; Harmonic filters; Insulation life; Power harmonic filters; Power system analysis computing; Power system harmonics; Power system simulation; Rail transportation; Substations; Voltage fluctuations; Harmonic analysis; power quality; rail transportation power systems;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/TPWRD.2006.873126
  • Filename
    1610698