  • Abstract
    This paper presents the details of a computationally efficient automatic voltage contingency selection algorithm developed for implementation at the AEP´s new system control center in Columbus, Ohio. The methodology is based on the quantification of the real-time system-wide impacts of the transmission branch (line and transformer) outages on the load bus voltage profile via the fast computation of a quadratic system Performance Index (PI) for every branch, and subsequent sorting of the results according to the severity of effects. The algotithm enjoys superior computational complexity compared to the previously published work. An application of the algorithm to the AEP EHV real-time data base is presented as an illustration.