• DocumentCode
    894204
  • Title

    Experimental Investigation of a Single-Phase UPQC With Minimum VA Loading

  • Author

    Kolhatkar, Yashomani Y. ; Das, Shyama P.

  • Author_Institution
    Indian Inst. of Technol., Kanpur
  • Volume
    22
  • Issue
    1
  • fYear
    2007
  • Firstpage
    373
  • Lastpage
    380
  • Abstract
    The paper deals with an optimized unified power-quality conditioner (UPQC), which aims at the integration of series active and shunt active power filters with minimum volt-ampere (VA) loading of the UPQC. The series active filter is a dynamic voltage restorer (DVR), which regulates the voltage at the load end with minimum VA loading of the overall UPQC by injecting the voltage at an optimum angle. The proposed scheme is validated by an experimental prototype in the laboratory. Selected experimental results are reported along with analytical findings, which show the effectiveness of the proposed UPQC
  • Keywords
    active filters; power harmonic filters; power supply quality; dynamic voltage restorer; series active filters; shunt active power filters; single phase unified power quality conditioner; volt-ampere loading; Active filters; Automatic voltage control; Electrical equipment industry; Power harmonic filters; Power quality; Power system harmonics; Programmable control; Pulse width modulation inverters; Reactive power; Voltage fluctuations; Optimum angle voltage injection; unified power-quality conditioner (UPQC); volt-ampere (VA) optimization; voltage sag;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/TPWRD.2006.881471
  • Filename
    4039442