DocumentCode :
901513
Title :
Axial electric-field measurements of d.c. arcs in current-limiting fuses
Author :
Ranjan, Rajiv ; Barrault, Michel R.
Author_Institution :
University of Liverpool, Department of Electrical Engineering & Electronics, Liverpool, UK
Volume :
127
Issue :
3
fYear :
1980
fDate :
5/1/1980 12:00:00 AM
Firstpage :
199
Lastpage :
202
Abstract :
The design of current-limiting fuses to meet the modern system requirements needs a thorough understanding of the fuse aic characteristics. In high-voltage fuse designs, a knowledge of the axial electric field and the speed of burn-back of the element will be useful to designers. This paper describes a method for measuring the axial electric field in the low overcurrent region of direct current arcs in current-limiting fuses. An arc model has been presented for the notched elements which shows that the electric field is inversely proportional to the thickness of lumen dimension.
Keywords :
arcs (electric); electric field measurement; electric fuses; limiters; DC arcs; arc model; axial electric field; current limiting fuses; direct current arcs; electric field measurements; fuse arc characteristics; high voltage fuse designs; low overcurrent region; notched elements;
fLanguage :
English
Journal_Title :
Generation, Transmission and Distribution, IEE Proceedings C
Publisher :
iet
ISSN :
0143-7046
Type :
jour
DOI :
10.1049/ip-c.1980.0030
Filename :
4643238
Link To Document :
بازگشت