DocumentCode
901818
Title
Harmonic reduction in d.c.-ripple reinjection
Author
Baird, J.F. ; Arrilaga, J.
Author_Institution
New Zealand Electricity, Christchurch, New Zealand
Volume
127
Issue
5
fYear
1980
fDate
9/1/1980 12:00:00 AM
Firstpage
294
Lastpage
303
Abstract
A d.c.- ripple reinjection principle is described which reduces the harmonic content produced by static convertors. It is shown by theory and experiment that, using this principle, a six-pulse convertor configuration can be made to operate as a twelve-pulse convertor from the point of view of a.c. and d.c. system harmonics. The reinjection circuit includes a feedback convertor in series with the d.c. output. This convertor provides automatic adjustment of the reinjected current as the load changes and improves the efficiency of the overall system.
Keywords
harmonics; power convertors; DC ripple reinjection; harmonic reduction; harmonics; reinjection circuit; static convertors;
fLanguage
English
Journal_Title
Generation, Transmission and Distribution, IEE Proceedings C
Publisher
iet
ISSN
0143-7046
Type
jour
DOI
10.1049/ip-c.1980.0046
Filename
4643273
Link To Document