• DocumentCode
    902523
  • Title

    Oxygen Deficiency Hazard Induced by Helium Release in Accelerator Tunnel

  • Author

    Brown, D.P. ; Sondericker, J.H.

  • Author_Institution
    Brookhaven National Laboratory Upton, New York 11973
  • Volume
    30
  • Issue
    4
  • fYear
    1983
  • Firstpage
    2898
  • Lastpage
    2900
  • Abstract
    Tests to investigate oxygen deficiency levels due to release of helium into the CBA tunnel are described. Results of the tests indicate that the helium stratifies and spreads quickly in the horizontal plane. This demonstrates that adequate warning of possible asphyxiation hazards can be achieved. When oxygen deficiency monitors are located at ceiling level they may be spaced at intervals of 60 m. or more and still achieve acceptable results.
  • Keywords
    Asphyxia; Fans; Hazards; Helium; Magnetic confinement; Magnetic heads; Magnetic sensors; Oxygen; Superconducting magnets; Testing;
  • fLanguage
    English
  • Journal_Title
    Nuclear Science, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9499
  • Type

    jour

  • DOI
    10.1109/TNS.1983.4336517
  • Filename
    4336517