  • Abstract
    The paper considers the steady-state performance of existing schemes of polyphase distance protection for high-voltage systems and introduces new polyphase schemes for phase and earth-fault protection. Differences in the performance of various schemes are highlighted and a comparison is given for close-up faults and zone 1 boundary faults. A new approach is suggested to assess the high-speed tripping characteristic of a polyphase unit and a method is given to establish whether or not high-speed protection is possible during close-up faults. Results of computer studies indicate that prefault load and power swings have a less marked effect on the reach of the new scheme during resistive faults, than is the case with a conventional 6-element scheme. Comparisons are also made with five switched-distance schemes supplied by relay manufacturers in Western Europe and the advantages and disadvantages of the polyphase approach are listed
  • Keywords
    electrical faults; relay protection; relays; boundary faults; close-up faults; high-voltage systems; phase and earth-fault protection; polyphase distance protection; polyphase schemes; relay; steady-state performance;
  • fLanguage
    English
  • Journal_Title
    Generation, Transmission and Distribution, IEE Proceedings C
  • Publisher
    iet
  • ISSN
    0143-7046
  • Type

    jour

  • DOI
    10.1049/ip-c.1981.0050
  • Filename
    4643414