    Survey osf TRV conditions on the CEGB 400kV system

  • Author

    Basak, P.K. ; Parrott, P.G.

  • Author_Institution
    Central Electricity Generating Board, System Technical Branch, London, UK
  • Volume
    128
  • Issue
    6
  • fYear
    1981
  • fDate
    11/1/1981 12:00:00 AM
  • Firstpage
    342
  • Lastpage
    350
  • Abstract
    The paper presents results of a survey of transient recovery voltage (TRV) on the CEGB 400 kV system, made by a series of digital-computer calculations, to provide a basis for the preparation of TRV parameters for a revised switchgear purcinising specification. The results are obtained for 3-phase earthed fault and single-phase-to-earth fault conditions. Details of the system represented in the survey are given, together with the method of representation and analysis of results. The relationship between fault current and rate of rise of TRV is discussed, and factors affecting peak voltage are considered
  • Keywords
    fault currents; switchgear; transient response; transmission networks; 3-phase earthed fault; 400 kV system; TRV parameters; digital-computer calculations; fault current; single phase to earth fault conditions; switchgear purchasing specification; transient recovery voltage;