• DocumentCode
    903199
  • Title

    Flowchart procedure to assess the condition of turbine generator insulation

  • Author

    Stone, G.C. ; Culbert, I. ; Dhirani, H.

  • Author_Institution
    Ontario Hydro, Toronto, Ont., Canada
  • Volume
    5
  • Issue
    3
  • fYear
    1990
  • fDate
    9/1/1990 12:00:00 AM
  • Firstpage
    546
  • Lastpage
    552
  • Abstract
    A method using flowcharts to indicate a step-by-step procedure to assess the insulation condition of turbine generators is presented. Information on likely deterioration processes which arise from the insulation-system characteristics and operating practices is collected. Online monitoring and offline tests are done to determine if problems could be occurring. Depending on the outcome of the previous steps, more extensive tests and detailed inspections usually requiring significant outages are performed. Although the procedure itself is straightforward, it is best implemented by engineers with considerable experience in this field. The flowcharts indicate to nonexperts the complexity of reliably assessing insulation condition
  • Keywords
    insulation testing; machine insulation; turbogenerators; flowcharts; insulation condition; offline tests; online monitoring; step-by-step procedure; turbine generator insulation; Dielectrics and electrical insulation; Flowcharts; Inspection; Insulation testing; Machine windings; Performance evaluation; Rotors; Stator windings; Thermal stresses; Turbines;
  • fLanguage
    English
  • Journal_Title
    Energy Conversion, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8969
  • Type

    jour

  • DOI
    10.1109/60.105280
  • Filename
    105280