DocumentCode :
904601
Title :
Fault location for transmission lines with current-transformer saturation
Author :
Richards, G.G. ; Tan, O.T.
Author_Institution :
Louisiana State University, Department of Electrical Engineering, Baton Rouge, USA
Volume :
130
Issue :
1
fYear :
1983
fDate :
1/1/1983 12:00:00 AM
Firstpage :
22
Lastpage :
27
Abstract :
The paper presents a fault-location method which is insensitive to current-transformer saturation. The method requires less than one cycle of recorded fault data, which do not need filtering. A parameter estimation technique is applied where the linear part of the reference model response is described by instantaneous symmetrical components and the nonlinear part, caused by transformer saturation, described by phase variables. The parameters identified by the estimator are fault distance, fault resistance and saturation parameters. Accuracy is demonstrated by digital simulation studies.
Keywords :
current transformers; digital simulation; fault location; power transmission lines; current-transformer saturation; digital simulation; fault distance; fault resistance; fault-location method; parameter estimation technique; saturation parameters; transmission lines;
fLanguage :
English
Journal_Title :
Generation, Transmission and Distribution, IEE Proceedings C
Publisher :
iet
ISSN :
0143-7046
Type :
jour
DOI :
10.1049/ip-c.1983.0004
Filename :
4643570
Link To Document :
بازگشت