DocumentCode
905912
Title
Performance characteristics of XLPE versus EPR as insulation for high voltage cables
Author
Chan, J.C. ; Hartley, Melissa D. ; Hiivala, L.J.
Author_Institution
Alcatel Canada Wire Inc., Toronto, Ont., Canada
Volume
9
Issue
3
fYear
1993
Firstpage
8
Lastpage
12
Abstract
The physical and electrical properties of crosslinked polyethylene (XLPE) and ethylene propylene rubber (EPR) are compared in the context of their use in transmission class cables. Results indicate that the 138-kV XLPE cable has AC withstand/breakdown strength at least 25% higher than the 150-kV EPR cable. The XLPE cable exhibits about 70% higher impulse strength than the EPR cable. The loss factor of the XLPE cable is at least 20 times lower than that of EPR cable. Thus with XLPE cables, the yearly energy savings can be on the order of 15 MWh/cct. km for a 69-kV system, 52 MWh/cct. km for a 138-kV system and 127 MHh/cct. km for a 230-kV system.<>
Keywords
cable insulation; dielectric losses; organic insulating materials; polymers; power cables; rubber; 138 to 230 kV; AC withstand; EPR; XLPE; breakdown strength; crosslinked polyethylene; electrical properties; ethylene propylene rubber; high voltage cables; impulse strength; loss factor; transmission class cables; Cable insulation; Cables; Costs; Dielectric losses; Dielectrics and electrical insulation; Environmental economics; Medium voltage; Paramagnetic resonance; Polyethylene; Power generation economics;
fLanguage
English
Journal_Title
Electrical Insulation Magazine, IEEE
Publisher
ieee
ISSN
0883-7554
Type
jour
DOI
10.1109/57.216782
Filename
216782
Link To Document