• DocumentCode
    905996
  • Title

    Current interruption by disconnecting switch and earthing switch in GIS

  • Author

    Suzuki, K. ; Mizoguchi, H. ; Shimokawara, N. ; Murayama, V. ; Yanabu, S.

  • Author_Institution
    Toshiba Corporation, Heavy Apparatus Engineering Laboratory, High Power Laboratory, Kawasaki, Japan
  • Volume
    131
  • Issue
    2
  • fYear
    1984
  • fDate
    3/1/1984 12:00:00 AM
  • Firstpage
    54
  • Lastpage
    60
  • Abstract
    Disconnecting switches (DS) and earthing switches (ES) in gas insulated substations (GIS) can be required to interrupt high currents, which are closed-loop currents for DS and electromagnetic induced current for ES.DS and ES must also have full dielectric strength, even after interrupting these high currents many times. An investigation of the interrupting capability of five types of extinction chambers has revealed that magnetic driving types are optimum for closed-loop current interruption and suction types are optimum for electromagnetic induced current interruption because of their simple construction and excellent performance
  • Keywords
    earthing; switches; switching substations; GIS; closed loop; current interruption; disconnecting switch; earthing switch; electromagnetic induced; extinction chambers; gas insulated substations; interrupting capability;
  • fLanguage
    English
  • Journal_Title
    Generation, Transmission and Distribution, IEE Proceedings C
  • Publisher
    iet
  • ISSN
    0143-7046
  • Type

    jour

  • DOI
    10.1049/ip-c.1984.0008
  • Filename