DocumentCode
905996
Title
Current interruption by disconnecting switch and earthing switch in GIS
Author
Suzuki, K. ; Mizoguchi, H. ; Shimokawara, N. ; Murayama, V. ; Yanabu, S.
Author_Institution
Toshiba Corporation, Heavy Apparatus Engineering Laboratory, High Power Laboratory, Kawasaki, Japan
Volume
131
Issue
2
fYear
1984
fDate
3/1/1984 12:00:00 AM
Firstpage
54
Lastpage
60
Abstract
Disconnecting switches (DS) and earthing switches (ES) in gas insulated substations (GIS) can be required to interrupt high currents, which are closed-loop currents for DS and electromagnetic induced current for ES.DS and ES must also have full dielectric strength, even after interrupting these high currents many times. An investigation of the interrupting capability of five types of extinction chambers has revealed that magnetic driving types are optimum for closed-loop current interruption and suction types are optimum for electromagnetic induced current interruption because of their simple construction and excellent performance
Keywords
earthing; switches; switching substations; GIS; closed loop; current interruption; disconnecting switch; earthing switch; electromagnetic induced; extinction chambers; gas insulated substations; interrupting capability;
fLanguage
English
Journal_Title
Generation, Transmission and Distribution, IEE Proceedings C
Publisher
iet
ISSN
0143-7046
Type
jour
DOI
10.1049/ip-c.1984.0008
Filename
4643717