• DocumentCode
    906182
  • Title

    Injected currents of controlled AC/DC converters for harmonic analysis in industrial power plants

  • Author

    Grotzbach, M. ; Frankenberg, Wolfgang

  • Author_Institution
    Dept. of Electr. Eng., Univ. of Federal Defence, Munich, Germany
  • Volume
    8
  • Issue
    2
  • fYear
    1993
  • fDate
    4/1/1993 12:00:00 AM
  • Firstpage
    511
  • Lastpage
    517
  • Abstract
    An easy method for predetermining the injected current harmonics of current-controlled six-pulse bridge converters is proposed. The parameters considered are the operating point of the converter, given by the DC mean current Id and EMF E, and two circuit parameters, AC network and DC reactance. When starting the predetermination, the operating point and the effective DC reactance have to be determined from the requirements of the applied DC loads. This leads to a uniform investigation of the controlled converter based on preliminary investigation reported elsewhere. As a result of systematic evaluations, the normalized line current harmonics are obtained graphically in the usual range of the parameters considered
  • Keywords
    bridge circuits; electric reactance; harmonics; power convertors; power plants; AC network reactance; DC mean current; DC reactance; controlled AC/DC converters; harmonic analysis; industrial power plants; normalized line current harmonics; six-pulse bridge converters; Circuits; DC-DC power converters; Harmonic analysis; Industrial control; Load flow analysis; Power generation; Power system harmonics; Pulse power systems; Steady-state; Voltage;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.216853
  • Filename
    216853