    Nonoptimum compensation schemes for single pole reclosing on EHV double circuit transmission lines

  • Author

    Thomann, Gary C. ; Lambert, Stephen R. ; Phaloprakarn, Somkiet

  • Volume
    8
  • Issue
    2
  • fYear
    1993
  • fDate
    4/1/1993 12:00:00 AM
  • Firstpage
    651
  • Lastpage
    659
  • Abstract
    Optimum reactor compensation configurations for implementing single pole reclosing on EHV (extra-high-voltage), double-circuit lines have been previously investigated. However, for some applications, optimum schemes may not be practical due to constraints such as reactor physical size, operating constraints and existing equipment. The performance of nonoptimum schemes is considered using an EGAT (Electricity Generating Authority of Thailand) 328 km, 500 kV, double-circuit line as an example. Several compensation schemes were considered, and their performance was examined with both circuits in service and with one circuit out for maintenance. The analysis indicated that some schemes with reactor values considerably off optimum still provided reasonable performance
  • Keywords
    compensation; power transmission lines; reactors (electric); 328 km; 500 kV; EHV double circuit transmission lines; Electricity Generating Authority of Thailand; reactor compensation; single pole reclosing; Capacitance; Circuit faults; Distributed parameter circuits; Inductors; Joining processes; Performance analysis; Power generation; Power transmission lines; Samarium; Voltage;