Design of a supplementary modulation control function for the Chester SVC
Author
Larsen, Einar ; Rostamkolai, Niusha ; Fisher, Doug ; Poitras, Alfred
Author_Institution
GE Ind. & Power Syst., Schenectady, NY, USA
Volume
8
Issue
2
fYear
1993
fDate
4/1/1993 12:00:00 AM
Firstpage
719
Lastpage
724
Abstract
The Chester static volt-ampere reactive (VAr) compensator (SVC) was recently installed in New England on the 345 kV interconnection between Maine and New Brunswick. This SVC provides dynamic voltage support to prevent the rejection of generation in New Brunswick following contingencies related to the phase II high-voltage direct-current (HVDC) interconnection between Quebec and New England. As the project evolved from the planning to design stages, a control function, referred to as the supplementary modulation control, became an important aspect of the overall SVC system. The criteria and analysis necessary to design this control function are described. Stability and subsynchronous torsional interaction are considered
Keywords
DC power transmission; power system control; power system interconnection; power system stability; static VAr compensators; 345 kV; 345 kV interconnection; Chester SVC; HVDC; Maine; New Brunswick; New England; Quebec; dynamic voltage support; high-voltage direct-current; stability; subsynchronous torsional interaction; supplementary modulation control; Control systems; HVDC transmission; Industrial power systems; Power system dynamics; Power system interconnection; Power system stability; Rivers; Sliding mode control; Static VAr compensators; Strontium;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/61.216880
Filename
216880
Link To Document