DocumentCode
908056
Title
Optimal placement of angle transducers in power systems
Author
Palmer, E.W. ; Ledwich, G.
Author_Institution
Queensland Univ. of Technol., Brisbane, Qld., Australia
Volume
11
Issue
2
fYear
1996
fDate
5/1/1996 12:00:00 AM
Firstpage
788
Lastpage
793
Abstract
This paper presents an algorithm which determines the best locations for placement of GPS (Global Positioning System) based voltage angle transducers. The sites are chosen so as to maximise their sensitivity to the lightly damped interarea modes while minimising their sensitivity to the more heavily damped local modes. Furthermore the algorithm used ensures that transducers are placed so as to give the greatest coverage of the various inter-area modes as possible giving modal estimates with a high degree of precision. A study made on a longitudinal 21 bus, 6 machine power system shows that the algorithm gives good results which are reasonable insensitive to system operating point. Caution is to be exercised in the application of this algorithm to meshed systems where mode shapes may depend on system operating point
Keywords
Global Positioning System; measurement theory; optimisation; power system interconnection; power system measurement; power system state estimation; transducers; voltage measurement; GPS; application; interarea modes; interconnection; local modes; measurement; modal estimates; monitoring; optimal placement algorithm; power systems; state estimation; voltage angle transducers; Damping; Global Positioning System; Power system analysis computing; Power system dynamics; Power system interconnection; Power system modeling; Power system stability; Power systems; Shape; Transducers; Voltage;
fLanguage
English
Journal_Title
Power Systems, IEEE Transactions on
Publisher
ieee
ISSN
0885-8950
Type
jour
DOI
10.1109/59.496155
Filename
496155
Link To Document