DocumentCode :
908061
Title :
Discharge detection techniques for stator windings
Author :
Wilson, A. ; Jackson, R.J. ; Wang, N.
Author_Institution :
Central Electricity Generating Board, Technology, Planning and Research Division, London, UK
Volume :
132
Issue :
5
fYear :
1985
fDate :
9/1/1985 12:00:00 AM
Firstpage :
234
Lastpage :
244
Abstract :
Partial-discharge measurements are being used increasingly to detect localised or damaged areas in modern high-voltage stator windings. However, ambiguities may arise because of the complex LC network between coils. Discharge pulses propagate in a variety of modes, each having different attenuation factors. Tests with diamond-wound motor stators and a 500 MW generator stator show that pulse detection in a limited frequency range, for example 20¿300 kHz, is most suitable. Here, attenuation errors are restricted to within a factor of two to three, whereas a wideband detection with the bandwidth in excess of 1 MHz may produce up to a 50-fold attenuation of signals from sites remote from the terminals of the stator windings. Electromagnetic probes and ultrasonic scanning techniques are useful for locating the sites of high discharge. Their accuracy and limits are reported.
Keywords :
electric machines; machine testing; partial discharges; stators; 500 MW generator stator; accuracy; attenuation; coils; diamond-wound motor stators; partial discharge measurement; pulse detection; stator windings; ultrasonic scanning; wideband detection;
fLanguage :
English