DocumentCode :
914116
Title :
New preventive measures against stray field of heavy current carrying conductors
Author :
Junyou, Yang ; Renyuan, Tang ; Chengyuan, Wang ; Meiwen, Zhou ; Yongbin, Chen
Author_Institution :
Shenyang Polytech. Univ., China
Volume :
32
Issue :
3
fYear :
1996
fDate :
5/1/1996 12:00:00 AM
Firstpage :
1489
Lastpage :
1492
Abstract :
The stray field of heavy current carrying conductors (HCCC) in large power transformers shows marked differences as compared to that of windings. New types of measures, separated magnetic steel plates welded on a nonmagnetic steel plate and closed loop shield, are presented to reduce the eddy current losses and to prevent the tank cover and walls from local overheating due to HCCC. Furthermore, the influences on the bolts and bushings are discussed. The BEM and FEM are employed to analyze the three dimensional eddy current field. Both numerical and experimental results show that no local overheating appears even if the phase current is up to 16 kA
Keywords :
boundary-elements methods; conductors (electric); eddy current losses; finite element analysis; power cables; power transformer testing; power transformers; 16 kA; 3D eddy current field; BEM; FEM; bolts; bushings; closed loop shield; experimental results; heavy current carrying conductors; large power transformers; local overheating; nonmagnetic steel plate; separated magnetic steel plates; stray field; Conductors; Current measurement; Eddy currents; Loss measurement; Magnetic field measurement; Magnetic separation; Magnetic shielding; Power transformers; Steel; Welding;
fLanguage :
English
Journal_Title :
Magnetics, IEEE Transactions on
Publisher :
ieee
ISSN :
0018-9464
Type :
jour
DOI :
10.1109/20.497531
Filename :
497531
Link To Document :
بازگشت