Resultant magnetic fields due to both windings and heavy current leads in large power transformers
Author :
Renyuan, Tang ; Yan, Li ; Feng, Lin ; Lijian, Tian
Author_Institution :
Shenyang Polytech. Univ., China
Volume :
32
Issue :
3
fYear :
1996
fDate :
5/1/1996 12:00:00 AM
Firstpage :
1641
Lastpage :
1644
Abstract :
The eddy current field due to both windings and heavy current leads (HCL) in large power transformers is analyzed by using the improved T-Ω method, in which T and Ω can be solved separately in different subregions. Thus, storage capacity and CPU time can be saved to a great extent. In addition, the local overheating on the tank wall near the magnetic shield gap is calculated and analyzed, and improvement measures are proposed. On the basis of this work, a composite shield is analyzed and optimized. The numerical results show that the eddy current losses are reduced and the local overheating is removed by using this composite shield
Keywords :
eddy current losses; magnetic fields; power engineering computing; power transformers; transformer windings; composite shield; computer simulation; eddy current field; eddy current losses; heavy current leads; improved T-Ω method; local overheating; magnetic fields; power transformers; windings; Clamps; Conductivity; Eddy currents; Equations; Magnetic analysis; Magnetic fields; Magnetic flux density; Magnetic separation; Magnetic shielding; Power transformers;
fLanguage :
English
Journal_Title :
Magnetics, IEEE Transactions on
Publisher :
ieee
ISSN :
0018-9464
Type :
jour
DOI :
10.1109/20.497569
Filename :
497569
Link To Document :
بازگشت