DocumentCode :
916511
Title :
Comparison of RTV silicone rubber coatings under artificial contamination in a fog chamber
Author :
Gorur, R.S. ; Karady, G.G. ; Jagota, A. ; Shah, M. ; Furumasu, B.C.
Author_Institution :
Dept. of Electr. Eng., Arizona State Univ., Tempe, AZ, USA
Volume :
7
Issue :
2
fYear :
1992
fDate :
4/1/1992 12:00:00 AM
Firstpage :
713
Lastpage :
719
Abstract :
A comparison is presented of the electrical performance of room-temperature vulcanized (RTV) silicone rubber coatings for insulators under artificial contamination produced in a salt-fog chamber with DC voltage. Comparison of the RTV coatings with silicone grease coating has also been made. Correlation of the electrical parameters, such as leakage current and flashover voltage, with material degradation due to aging produced by dry band arcing is established. It is demonstrated that there are distinct differences among the RTV coatings evaluated, and between RTV coatings and silicon grease
Keywords :
insulation testing; insulators; rubber; silicones; DC voltage; RTV silicone rubber coatings; aging; artificial contamination; dry band arcing; flashover voltage; fog chamber; insulators; leakage current; silicone grease coating; Aging; Arc discharges; Coatings; Contamination; Degradation; Dielectrics and electrical insulation; Flashover; Leakage current; Rubber; Voltage;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/61.127072
Filename :
127072
Link To Document :
بازگشت