• DocumentCode
    917357
  • Title

    Spiral arc quenching

  • Author

    Kolacinski, Z. ; Campbell, L.C. ; Zdanowicz, L.S.

  • Author_Institution
    Tech. Univ. of Lodz, Poland
  • Volume
    7
  • Issue
    2
  • fYear
    1992
  • fDate
    4/1/1992 12:00:00 AM
  • Firstpage
    822
  • Lastpage
    828
  • Abstract
    A description of the general behavior of an atmospheric pressure AC and DC spiral arc, during interruption in a narrow cylindrical slot, is presented. The arc duration time and overvoltage have been measured, as a function of magnetic flux density, arc current, slot width, and electrode gap, for different electrode arrangements. Multichannel optical fiber probes and a two-line spectroscopic method have been used for arc temperature measurement and the spatial spread of the arc wake has been determined, along with some associated phenomena
  • Keywords
    circuit breakers; circuit-breaking arcs; fibre optic sensors; overvoltage; temperature measurement; voltage measurement; DC spiral arc; arc current; arc duration time; arc temperature measurement; arc wake spatial spread; atmospheric pressure; circuit breakers; electrode gap; magnetic flux density; multichannel optical fibre probes; narrow cylindrical slot; overvoltage; slot width; spiral arc quenching; two-line spectroscopic method; Atmospheric measurements; Current measurement; Density measurement; Electrodes; Magnetic flux density; Optical fibers; Probes; Spirals; Time measurement; Voltage control;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.127086
  • Filename
    127086