    Distribution feeder modification to service both sensitive loads and large drives

  • Author

    Morgan, Larry ; Ihara, Satoru

  • Author_Institution
    Duke Power Co., Charlotte, NC, USA
  • Volume
    7
  • Issue
    2
  • fYear
    1992
  • fDate
    4/1/1992 12:00:00 AM
  • Firstpage
    883
  • Lastpage
    887
  • Abstract
    An intermittent load consisting of large adjustable speed drives had to be added to an existing 24 kV feeder for office buildings equipped with computers of various types. A standard option of constructing a new substation or a new transmission feeder was not possible due to environmental concerns. Consequently, the existing feeder had to be modified through innovative application of a specially designed harmonic filter and a distribution series capacitor so that harmonic problems, voltage flicker problems, and commutation notch problems could be avoided. The technical aspects of the problems and solutions are presented. In addition, the cooperation required between the utility and the customer is discussed
  • Keywords
    distribution networks; filters; harmonics; variable speed drives; 24 kV; adjustable speed drives; commutation notch problems; distribution feeder modification; distribution series capacitor; harmonic filter; harmonic problems; intermittent load; sensitive loads; voltage flicker problems; Capacitors; Commutation; Drives; Power quality; Reactive power; Substations; Test facilities; Transformers; Varistors; Voltage fluctuations;