• DocumentCode
    917474
  • Title

    Development and application of the 275 kV 300 MVA separate-cooling, sheet-winding gas-insulated transformer

  • Author

    Muramoto, H. ; Yamazaki, T. ; Oshi, T. ; Uehara, K. ; Toda, K. ; Ikeda, M. ; Yanabu, S.

  • Author_Institution
    Tokyo Electric Power Co. Ltd., Japan
  • Volume
    7
  • Issue
    2
  • fYear
    1992
  • fDate
    4/1/1992 12:00:00 AM
  • Firstpage
    888
  • Lastpage
    894
  • Abstract
    In 1989, a 154 kV, 200 MVA gas-insulated power transformer was commissioned and has been operated with a satisfactory operating record. Utilizing this development experience and introducing new technology, a 275 kV, 300 MVA gas-insulated power transformer has been developed. The compact design of the main-gap insulation is important, and its reliability has been verified. The turn-to-turn insulation, which is made of PET film insulation has also been verified under severely stressed test conditions. The design of the 300 MVA gas-insulated transformer is described
  • Keywords
    gaseous insulation; organic insulating materials; polymers; power transformers; reliability; transformer insulation; transformer windings; 275 kV; 300 MVA; PET film insulation; gas-insulated transformer; main-gap insulation; polyethylene terephthalate; reliability; sheet-winding; turn-to-turn insulation; Cities and towns; Fires; Gas insulation; Oil insulation; Positron emission tomography; Power supplies; Power system reliability; Power transformer insulation; Power transformers; Substations;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.127095
  • Filename
    127095