Overcurrent protection of capacitors applied on industrial distribution systems
Author
Mendis, S.R. ; Bishop, M.T. ; McCall, J.C. ; Hurst, W.M.
Author_Institution
Cooper Power Syst., Franksville, WI, USA
Volume
29
Issue
3
fYear
1993
Firstpage
541
Lastpage
547
Abstract
The protection of power factor correction capacitors used to enhance electrical system efficiency is addressed. Different considerations in the selection of capacitor fuse applications and the philosophies behind them are reviewed. Individual and group fusing are discussed. Continuous current, transient current, fault current, tank rupture curve coordination, voltage on good capacitors during a fault, energy discharged into a failed unit, outrush current, and coordination with unbalance detection schemes are topics covered. Examples of actual applications of capacitors in industrial distribution systems are presented
Keywords
distribution networks; fault currents; overcurrent protection; power capacitors; power factor correction; power system protection; transients; capacitor fuse; continuous current; electrical system efficiency; fault current; group fusing; industrial distribution systems; power factor correction capacitors; tank rupture curve coordination; transient current; unbalance detection schemes; ANSI standards; Furnaces; Fuses; Industrial plants; Power capacitors; Power harmonic filters; Power system harmonics; Power system protection; Reactive power; Voltage;
fLanguage
English
Journal_Title
Industry Applications, IEEE Transactions on
Publisher
ieee
ISSN
0093-9994
Type
jour
DOI
10.1109/28.222424
Filename
222424
Link To Document