• DocumentCode
    921029
  • Title

    Voltage control of parallel operated self excited induction generators

  • Author

    Al-Bahrani, A.H. ; Malik, N.H.

  • Author_Institution
    Dept. of Electr. Eng., King Saud Univ., Riyadh, Saudi Arabia
  • Volume
    8
  • Issue
    2
  • fYear
    1993
  • fDate
    6/1/1993 12:00:00 AM
  • Firstpage
    236
  • Lastpage
    242
  • Abstract
    Two methods of analysis are proposed for use in the control of the common bus voltage of any number of parallel self-excited induction generators (SEIGs) under steady state balanced conditions. The methods are general and can be used for a single SEIG or a group of SEIGs employing similar or different machines with equal or unequal prime mover speeds. Theoretical predictions of the two models have been verified experimentally. Using these methods, effects of various parameters on the voltage control characteristics are examined for a number of cases employing similar and different SEIGs at equal and unequal speeds
  • Keywords
    asynchronous generators; control system analysis; exciters; machine control; machine theory; voltage control; common bus voltage; control system analysis; machine control; prime mover; self excited induction generators; voltage control; Capacitors; Costs; Educational institutions; Induction generators; Predictive models; Robustness; Rotors; Steady-state; Voltage control; Wind energy generation;
  • fLanguage
    English
  • Journal_Title
    Energy Conversion, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8969
  • Type

    jour

  • DOI
    10.1109/60.222710
  • Filename
    222710