DocumentCode
921318
Title
Stall protection of large induction motors
Author
DeCastro, Jose E. ; Beck, Roy T. ; Cai, Charles ; Yu, Luke
Author_Institution
Ralph M. Parsons Co., Pasadena, CA, USA
Volume
31
Issue
5
fYear
1995
Firstpage
1159
Lastpage
1166
Abstract
Large induction motors driving high inertia loads, such as fans, blowers, and reciprocating compressors, may take a longer time to accelerate to full speed than their allowable (safe) stall time. This paper discusses the available types of stall protection for motors whose starting time exceeds their allowable stall time
Keywords
compressors; induction motor protection; load (electric); relay protection; starting; blowers; fans; high inertia loads; induction motors; reciprocating compressors; stall protection; stall time; starting time; Acceleration; Chemical industry; Induction motors; Insulation; Petroleum; Protection; Rotors; Stator windings; Temperature; Voltage;