• DocumentCode
    923697
  • Title

    Frequency scanning for power system property Determination-applied to a wind power grid

  • Author

    Thiringer, Torbjörn

  • Author_Institution
    Div. of Electr. Power Eng., Chalmers Univ. of Technol., Goteborg, Sweden
  • Volume
    21
  • Issue
    2
  • fYear
    2006
  • fDate
    5/1/2006 12:00:00 AM
  • Firstpage
    702
  • Lastpage
    708
  • Abstract
    This paper presents an investigation of a method for determining the dynamic properties of a power system. The investigation is based on the injection of perturbations in the supply voltage magnitude and the analysis of the resulting active and reactive power responses. A large dc/ac converter (HVDC-Light installation) has been used to generate the perturbations. The frequency range of the perturbations was from 0.03 to 20 Hz. The method is experimentally verified on a small 10-kV grid with 5 MW of wind power, subjected to the above perturbations. Both theoretical and experimental results indicate that a large concentration of wind turbines does not cause any power quality disturbances or serious oscillations, although the grid is fairly weak.
  • Keywords
    DC-AC power convertors; power supply quality; wind power plants; wind turbines; 0.03 to 20 Hz; 10 kV; 5 MW; HVDC-light installation; active power response; dc-ac converter; frequency scanning; perturbations injection; power system property determination; reactive power response; wind power grid; wind turbines; AC generators; Analog-digital conversion; DC generators; Frequency; Power system analysis computing; Power system dynamics; Power systems; Reactive power; Voltage; Wind energy; Grid interaction; model; modeling; power quality; wind turbine;
  • fLanguage
    English
  • Journal_Title
    Power Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8950
  • Type

    jour

  • DOI
    10.1109/TPWRS.2006.873102
  • Filename
    1626374